1、鍋爐房內的設備布置應便于操作、通行和檢修。
Boiler room equipment should be arranged for easy operation, access and maintenance.
2、鍋爐房應有足夠的照明和良好的通風以及必要的降溫和防凍措施。
Boiler room should have adequate lighting and ventilation as well as the necessary
cooling and freezing measures.
3、鍋爐房應防止積水。
Boiler room should prevent accumulation of water.
4、鍋爐房地面應平整無臺階。
Boiler room floor should be smooth and without steps.
5、鍋爐房承重梁柱等構件與鍋爐應有一定距離或采取其他措施,以防受高溫損壞。
Load-bearing beams and other components of the boiler room and the boiler should be a
certain distance or take other measures to prevent damage by high temperatures.
6、鍋爐房每層至少有兩個出口,分別設在兩側。鍋爐前端的總寬度不超過12m,且面積不超過200
平方米的單層鍋爐,可以只開一個出口。
Boiler room each have at least two exits are located on both sides. The total width of the front of the boiler does not exceed 12m, and the area does not exceed 200 square meters of single-7, layer boilers, can only open an exit.
7、鍋爐房通向室外的門應向外開,在鍋爐運行期間不準鎖住或閂住。鍋爐房內工作室或生活室的
門應向鍋爐房內開。鍋爐房的出入口和通道應暢通無阻。在鍋爐房內的操作地點及水位表、壓力
表、溫度計、流量計等處,應有足夠的照明。鍋爐房應有備用的照明設備或工具。
Leading to the boiler room doors should open outwards outdoors during boiler operation allowed locked or bolted. Boiler room studio or living room boiler room door should open. Boiler room entrances and channels should open. In the boiler room operation location and water table, pressure gauges, mometers, flow meters, etc. should have adequate lighting. Boiler room should spare lighting equipment or tools.